Pular para o conteúdo principal

Parametrização do Equipamento

EquipamentoAcessório NecessárioTipo de ConexãoDriverParâmetroDescriçãoRecomendado ou Ajuste de Fábrica
CFW300CFW300 + CFW300-CRS232 moduleRS232- - - -0308Serial Address1
CFW300CFW300 + CFW300-CRS232 moduleRS232- - - -0310Serial Baud Rate1 = 19200 bits/s
CFW300CFW300 + CFW300-CRS232 moduleRS232- - - -0311Serial Byte Configuration1 = 8 bits, even, 1 sb
CFW300CFW300 + CFW300-CRS232 moduleRS232- - - -0312Serial Protocol2 = Modbus RTU
CFW300CFW300 + CFW300-CRS485 moduleRS485USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)0308Serial Address1
CFW300CFW300 + CFW300-CRS485 moduleRS485USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)0310Serial Baud Rate1 = 19200 bits/s
CFW300CFW300 + CFW300-CRS485 moduleRS485USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)0311Serial Byte Configuration1 = 8 bits, even, 1 sb
CFW300CFW300 + CFW300-CRS485 moduleRS485USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)0312Serial Protocol2 = Modbus RTU
CFW300CFW300 + CFW300-CUSB modulePorta Serial USBFTDI0308Serial Address1
CFW300CFW300 + CFW300-CUSB modulePorta Serial USBFTDI0310Serial Baud Rate1 = 19200 bits/s
CFW300CFW300 + CFW300-CUSB modulePorta Serial USBFTDI0311Serial Byte Configuration1 = 8 bits, even, 1 sb
CFW300CFW300 + CFW300-CUSB modulePorta Serial USBFTDI0312Serial Protocol2 = Modbus RTU
CFW300CFW300 + CFW300-CETH moduleEthernet- - - -0850IP Address Config1 = DHCP
CFW300CFW300 + CFW300-CETH moduleEthernet- - - -0855CIDR Sub-net24 = 255.255.255.0
CFW300CFW300 + CFW300-CETH moduleEthernet- - - -0856Gateway 10
CFW300CFW300 + CFW300-CETH moduleEthernet- - - -0857Gateway 20
CFW300CFW300 + CFW300-CETH moduleEthernet- - - -0858Gateway 30
CFW300CFW300 + CFW300-CETH moduleEthernet- - - -0859Gateway 40
CFW300CFW300 + CFW300-CETH moduleEthernet- - - -0865MBTCP: TCP Port502
CFW300CFW300 + CFW300-CETH moduleEthernet- - - -0868MBTCP: Timeout0
CFW320CFW320 + CFW320-CRS232 moduleRS232- - - -0308Serial Address1
CFW320CFW320 + CFW320-CRS232 moduleRS232- - - -0310Serial Baud Rate1 = 19200 bits/s
CFW320CFW320 + CFW320-CRS232 moduleRS232- - - -0311Serial Byte Configuration1 = 8 bits, even, 1 sb
CFW320CFW320 + CFW320-CRS232 moduleRS232- - - -0312Serial Protocol2 = Modbus RTU
CFW320CFW320 + CFW320-CRS485 moduleRS485USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)0308Serial Address1
CFW320CFW320 + CFW320-CRS485 moduleRS485USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)0310Serial Baud Rate1 = 19200 bits/s
CFW320CFW320 + CFW320-CRS485 moduleRS485USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)0311Serial Byte Configuration1 = 8 bits, even, 1 sb
CFW320CFW320 + CFW320-CRS485 moduleRS485USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)0312Serial Protocol2 = Modbus RTU
CFW320CFW320 + CFW320-CUSB modulePorta Serial USBFTDI0308Serial Address1
CFW320CFW320 + CFW320-CUSB modulePorta Serial USBFTDI0310Serial Baud Rate1 = 19200 bits/s
CFW320CFW320 + CFW320-CUSB modulePorta Serial USBFTDI0311Serial Byte Configuration1 = 8 bits, even, 1 sb
CFW320CFW320 + CFW320-CUSB modulePorta Serial USBFTDI0312Serial Protocol2 = Modbus RTU
CFW320CFW320 + CFW320-CETH moduleEthernet- - - -0850IP Address Config1 = DHCP
CFW320CFW320 + CFW320-CETH moduleEthernet- - - -0855CIDR Sub-net24 = 255.255.255.0
CFW320CFW320 + CFW320-CETH moduleEthernet- - - -0856Gateway 10
CFW320CFW320 + CFW320-CETH moduleEthernet- - - -0857Gateway 20
CFW320CFW320 + CFW320-CETH moduleEthernet- - - -0858Gateway 30
CFW320CFW320 + CFW320-CETH moduleEthernet- - - -0859Gateway 40
CFW320CFW320 + CFW320-CETH moduleEthernet- - - -0865MBTCP: TCP Port502
CFW320CFW320 + CFW320-CETH moduleEthernet- - - -0868MBTCP: Timeout0
CFW-11- - - -Porta Serial USBFTDI0308Serial Address1
CFW-11- - - -Porta Serial USBFTDI0310Serial Baud Rate1 = 19200 bits/s
CFW-11- - - -Porta Serial USBFTDI0311Serial Byte Configuration1 = 8 bits, even, 1 sb
CFW-11- - - -Porta Serial USBFTDI0312Serial Protocol2 = Modbus RTU
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0841Eth:Baud rate0 = Auto
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0842Eth:Modbus TCP Timeout0
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0843Eth:IP Address Config1 = DHCP
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0848Eth:CIDR Sub-net24 = 255.255.255.0
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0849Eth:Gateway 10
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0850Eth:Gateway 20
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0851Eth:Gateway 30
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0852Eth:Gateway 40
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0853Station Name0
CFW-11CFW-11 + ETHERNET IP-05 moduleEthernet- - - -0854Compatible mode0 = Modbus WEG
CFW500CFW500 + CFW500-CRS232 moduleRS232- - - -0308Serial Address1
CFW500CFW500 + CFW500-CRS232 moduleRS232- - - -0310Serial Baud Rate1 = 19200 bits/s
CFW500CFW500 + CFW500-CRS232 moduleRS232- - - -0311Serial Byte Configuration1 = 8 bits, even, 1 sb
CFW500CFW500 + CFW500-CRS232 moduleRS232- - - -0312Serial Protocol2 = Modbus RTU (1)
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0803Ethernet Baud Rate0 = Auto
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0806Modbus TCP Watchdog0
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0810IP Address Configuration1 = DHCP
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0815Subnet CIDR24 = 255.255.255.0
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0816Gateway 10
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0817Gateway 20
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0818Gateway 30
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0819Gateway 40
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0820..0831Ethernet Read Words #3..#140
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0835..0846Ethernet Write Words #3..#140
CFW500CFW500 + CFW500-CETH-IP moduleEthernet- - - -0849Update Ethernet Configuration0 = Normal Operation
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 port module)Ethernet- - - -0799Eth: Enable Protocols (1 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 port module)Ethernet- - - -0800Eth: Module Identification (1 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 port module)Ethernet- - - -0801Eth: Communication status (1 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 port module)Ethernet- - - -0803Eth: Communication baudrate (1 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 port module)Ethernet- - - -0849Eth: Update Configuration (1 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0806Eth: Timeout modbus TCP (1;2 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0810Eth: Config IP Address (1;2 p)1 = DHCP
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0811Eth: IP address 1 (1;2 p)192
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0812Eth: IP address 2 (1;2 p)168
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0813Eth: IP address 3 (1;2 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0814Eth: IP address 4 (1;2 p)14
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0815Eth: CIDR subnet (1;2 p)24: 255.255.255.0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0816Eth: Gateway 1 (1;2 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0817Eth: Gateway 2 (1;2 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0818Eth: Gateway 3 (1;2 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0819Eth: Gateway 4 (1;2 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0820Eth: Read #3 (1;2 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (1 or 2 ports module)Ethernet- - - -0821Eth: Read #4 (1;2 p)0
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0856Eth: IP address 1 (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0857Eth: IP address 2 (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0858Eth: IP address 3 (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0859Eth: IP address 4 (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0860MBTCP: Communication status (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0863MBTCP: Active connections (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0865MBTCP: TCP port (2 p)502
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0869EIP: Master state (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0870EIP: Communication status (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0871EIP: Data profile (2 p)8 = 100/150: Manufac. Speed + I/O
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0886EIP: DLR topology (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0887EIP: DLR state (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0889EIP: Interface status (2 p)-
CFW500-CETH-2CFW500 + CFW500-CETH-2 module (2 ports module)Ethernet- - - -0890EIP: Interface control (2 p)9
SCA06- - - -USBWEG USB Driver- - - -- - - - -- - - - -
SCA06SCA06 + ECO4 moduleEthernet- - - -0803Eth:Baud rate0 = Auto
SCA06SCA06 + ECO4 moduleEthernet- - - -0806Eth:Modbus TCP Timeout0
SCA06SCA06 + ECO4 moduleEthernet- - - -0810Eth:IP Address Config1 = DHCP
SCA06SCA06 + ECO4 moduleEthernet- - - -0815Eth:CIDR Sub-net24 = 255.255.255.0
SCA06SCA06 + ECO4 moduleEthernet- - - -0816Eth:Gateway 10
SCA06SCA06 + ECO4 moduleEthernet- - - -0817Eth:Gateway 20
SCA06SCA06 + ECO4 moduleEthernet- - - -0818Eth:Gateway 30
SCA06SCA06 + ECO4 moduleEthernet- - - -0819Eth:Gateway 40
SCA06SCA06 + ECO4 moduleEthernet- - - -0820..0831Eth:Read Word #5..#160
SCA06SCA06 + ECO4 moduleEthernet- - - -0835..0846Eth:Write Word #5..#160
SCA06SCA06 + ECO4 moduleEthernet- - - -0849Eth:Configuration Update0 = Normal Operation
PLC300- - - -USBWEG USB Driver- - - -- - - - -- - - - -
SSW900- - - -USBWEG USB Driver- - - -- - - - -- - - - -
SSW900SSW900 + SSW900-CETH-IP-N moduleEthernet

ℹ️ Nota: Parâmetros podem variar por firmware. Consulte sempre o manual do fabricante WEG para confirmar os valores corretos e parâmetros adicionais.