Os seguintes parâmetros devem ser ajustados para estabelecer a comunicação com os equipamentos:

 

Equipamento

Acessório Necessário

Tipo de Conexão

Driver

Parâmetro

Descrição

Recomendado ou Ajuste de Fábrica

CFW300

CFW300 + CFW300-CRS232 module

RS232

- - - -

0308

Serial Address

1

0310

Serial Baud Rate

1 = 19200 bits/s

0311

Serial Byte Configuration

1 = 8 bits, par, 1 sb

0312

Serial Protocol

2 = Modbus RTU

CFW300 + CFW300-CRS485 module

RS485

USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device)

0308

Serial Address

1

0310

Serial Baud Rate

1 = 19200 bits/s

0311

Serial Byte Configuration

1 = 8 bits, par, 1 sb

0312

Serial Protocol

2 = Modbus RTU

CFW300 + CFW300-CUSB module

Porta Serial USB

FTDI

0308

Serial Address

1

0310

Serial Baud Rate

1 = 19200 bits/s

0311

Serial Byte Configuration

1 = 8 bits, par, 1 sb

0312

Serial Protocol

2 = Modbus RTU

CFW300 + CFW300-CETH module

Ethernet

- - - -

0850

IP Address Config

1 = DHCP

0855

CIDR Sub-net

24 = 255.255.255.0

0856

Gateway 1

0

0857

Gateway 2

0

0858

Gateway 3

0

0859

Gateway 4

0

0865

MBTCP: TCP Port

502

0868

MBTCP: Timeout

0

CFW-11

- - - -

Porta Serial USB

FTDI

0308

Serial Address

1

0310

Serial Baud Rate

1 = 19200 bits/s

0311

Serial Byte Configuration

1 = 8 bits, par, 1 sb

0312

Serial Protocol

2 = Modbus RTU

CFW-11 + ETHERNET IP-05 module

Ethernet

- - - -

0841

Eth:Baud rate

0 = Auto

0842

Eth:Modbus TCP Timeout

0

0843

Eth:IP Address Config

1 = DHCP

0848

Eth:CIDR Sub-net

24 = 255.255.255.0

0849

Eth:Gateway 1

0

0850

Eth:Gateway 2

0

0851

Eth:Gateway 3

0

0852

Eth:Gateway 4

0

0853

Station Name

0

0854

Compatible mode

0 = Modbus WEG

CFW500

CFW500 + CFW500-CRS232 module

RS232

- - - -

0308

Serial Address

1

0310

Serial Baud Rate

1 = 19200 bits/s

0311

Serial Byte Configuration

1 = 8 bits, par, 1 sb

0312

Serial Protocol

2 = Modbus RTU (1)

CFW500 + CFW500-CETH-IP module

Ethernet

- - - -

0803

Ethernet Baud Rate

0 = Auto

0806

Modbus TCP Watchdog

0

0810

IP Address Configuration

1 = DHCP

0815

Subnet CIDR

24 = 255.255.255.0

0816

Gateway 1

0

0817

Gateway 2

0

0818

Gateway 3

0

0819

Gateway 4

0

0820..0831

Ethernet Read Words #3..#14

0

0835..0846

Ethernet Write Words #3..#14

0

0849

Update Ethernet Configuration

0 = Normal Operation

SCA06

- - - -

USB

WEG USB Driver

- - - -

- - - - -

- - - - -

SCA06 + ECO4 module

Ethernet

- - - -

0803

Eth:Baud rate

0 = Auto

0806

Eth:Modbus TCP Timeout

0

0810

Eth:IP Address Config

1 = DHCP

0815

Eth:CIDR Sub-net

24 = 255.255.255.0

0816

Eth:Gateway 1

0

0817

Eth:Gateway 2

0

0818

Eth:Gateway 3

0

0819

Eth:Gateway 4

0

0820..0831

Eth:Read Word #5..#16

0

0835..0846

Eth:Write Word #5..#16

0

0849

Eth:Configuration Update

0 = Normal Operation

PLC300

- - - -

USB

WEG USB Driver

- - - -

- - - - -

- - - - -

SSW900

- - - -

USB

WEG USB Driver

- - - -

- - - - -

- - - - -

SSW900 + SSW900-CETH-IP-N module

Ethernet

- - - -

C8.3.1

Update Configuration

0 = Normal Operation

C8.3.2

Address

63

C8.3.3

Baud Rate

3 = Autobaud

C8.3.4

IP Address Configuration

1 = DHCP

C8.3.5

IP Address

0.0.0.0

C8.3.6

CIDR

24 = 255.255.255.0

C8.3.7

Gateway

0.0.0.0

C8.3.8

Station Name Suffix

0

 