The following parameters must be set so as to establish the communication with the equipments:
Equipment |
Required Accessory |
Connection Type |
Driver |
Parameter |
Description |
Recommended or Factory Setting |
|---|---|---|---|---|---|---|
CFW100 |
CFW100 + CFW100-CRS485 module |
USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device) |
0308 |
Serial Address |
1 |
|
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW100 + CFW100-CUSB module |
FTDI |
0308 |
Serial Address |
1 |
||
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW300
CFW300-2 |
CFW300 + CFW300-CRS232 module |
- - - - |
0308 |
Serial Address |
1 |
|
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW300 + CFW300-CRS485 module |
USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device) |
0308 |
Serial Address |
1 |
||
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW300 + CFW300-CUSB module |
FTDI |
0308 |
Serial Address |
1 |
||
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW300 + CFW300-CETH module |
- - - - |
0850 |
IP Address Config |
1 = DHCP |
||
0855 |
CIDR Sub-net |
24 = 255.255.255.0 |
||||
0856 |
Gateway 1 |
0 |
||||
0857 |
Gateway 2 |
0 |
||||
0858 |
Gateway 3 |
0 |
||||
0859 |
Gateway 4 |
0 |
||||
0865 |
MBTCP: TCP Port |
502 |
||||
0868 |
MBTCP: Timeout |
0 |
||||
CFW320 |
CFW320 + CFW320-CRS232 module |
- - - - |
0308 |
Serial Address |
1 |
|
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW320 + CFW320-CRS485 module |
USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device) |
0308 |
Serial Address |
1 |
||
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW320 + CFW320-CUSB module |
FTDI |
0308 |
Serial Address |
1 |
||
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW320 + CFW320-CETH module |
- - - - |
0850 |
IP Address Config |
1 = DHCP |
||
0855 |
CIDR Sub-net |
24 = 255.255.255.0 |
||||
0856 |
Gateway 1 |
0 |
||||
0857 |
Gateway 2 |
0 |
||||
0858 |
Gateway 3 |
0 |
||||
0859 |
Gateway 4 |
0 |
||||
0865 |
MBTCP: TCP Port |
502 |
||||
0868 |
MBTCP: Timeout |
0 |
||||
CFW-11 |
- - - - |
FTDI |
0308 |
Serial Address |
1 |
|
0310 |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU |
||||
CFW-11 + ETHERNET IP-05 module |
- - - - |
0841 |
Eth:Baud rate |
0 = Auto |
||
0842 |
Eth:Modbus TCP Timeout |
0 |
||||
0843 |
Eth:IP Address Config |
1 = DHCP |
||||
0848 |
Eth:CIDR Sub-net |
24 = 255.255.255.0 |
||||
0849 |
Eth:Gateway 1 |
0 |
||||
0850 |
Eth:Gateway 2 |
0 |
||||
0851 |
Eth:Gateway 3 |
0 |
||||
0852 |
Eth:Gateway 4 |
0 |
||||
0853 |
Station Name |
0 |
||||
0854 |
Compatible mode |
0 = Modbus WEG |
||||
CFW500
CFW501
CFW503
MW500 |
CFW500 + CFW500-CRS232 module |
- - - - |
0308 |
Serial Address |
1 |
|
0310 * |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 * |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU (1) |
||||
CFW500 + CFW500-CRS485 module |
USB drive supplied by the manufacturer of the Isolated USB to 485 Converter (external device) |
0308 |
Serial Address |
1 |
||
0310 * |
Serial Baud Rate |
1 = 19200 bits/s |
||||
0311 * |
Serial Byte Configuration |
1 = 8 bits, even, 1 sb |
||||
0312 |
Serial Protocol |
2 = Modbus RTU (1) |
||||
CFW500 + CFW500-CETH-IP module |
- - - - |
0803 |
Ethernet Baud Rate |
0 = Auto |
||
0806 |
Modbus TCP Watchdog |
0 |
||||
0810 |
IP Address Configuration |
1 = DHCP |
||||
0815 |
Subnet CIDR |
24 = 255.255.255.0 |
||||
0816 |
Gateway 1 |
0 |
||||
0817 |
Gateway 2 |
0 |
||||
0818 |
Gateway 3 |
0 |
||||
0819 |
Gateway 4 |
0 |
||||
0820..0831 |
Ethernet Read Words #3..#14 |
0 |
||||
0835..0846 |
Ethernet Write Words #3..#14 |
0 |
||||
0849 |
Update Ethernet Configuration |
0 = Normal Operation |
||||
CFW500-CETH-2 |
CFW500 + CFW500-CETH-2 module
* (1 p) 1 port module * (2 p) 2 ports module * (1;2 p) 1 or 2 ports modules |
- - - - |
0799 |
Eth: Enable Protocols (1 p)* |
0 |
|
0806 |
Eth: Timeout modbus TCP (1;2 p)* |
0 |
||||
0810 |
Eth: Config IP Address (1;2 p)* |
1 = DHCP |
||||
0811 |
Eth: IP address 1 (1;2 p)* |
192 |
||||
0812 |
Eth: IP address 2 (1;2 p)* |
168 |
||||
0813 |
Eth: IP address 3 (1;2 p)* |
0 |
||||
0814 |
Eth: IP address 4 (1;2 p)* |
14 |
||||
0815 |
Eth: CIDR subnet (1;2 p)* |
24: 255.255.255.0 |
||||
0816 |
Eth: Gateway 1 (1;2 p)* |
0 |
||||
0817 |
Eth: Gateway 2 (1;2 p)* |
0 |
||||
0818 |
Eth: Gateway 3 (1;2 p)* |
0 |
||||
0819 |
Eth: Gateway 4 (1;2 p)* |
0 |
||||
0820 .. 0831 |
Eth: Read #3 .. Eth: Read #14 (1;2 p)* |
0 |
||||
0835 .. 0846 |
Eth: Write #3 .. Eth: Write #14 (1;2 p)* |
0 |
||||
0856 |
Eth: IP address 1 (2 p)* |
- |
||||
0857 |
Eth: IP address 2 (2 p)* |
- |
||||
0858 |
Eth: IP address 3 (2 p)* |
- |
||||
0859 |
Eth: IP address 4 (2 p)* |
- |
||||
0860 |
MBTCP: Communication status (2 p)* |
- |
||||
0863 |
MBTCP: Active connections (2 p)* |
- |
||||
0865 |
MBTCP: TCP port (2 p)* |
502 |
||||
0869 |
EIP: Master state (2 p)* |
- |
||||
0870 |
EIP: Communication status (2 p)* |
- |
||||
0871 |
EIP: Data profile (2 p)* |
8 = 100/150: Manufac. Speed + I/O |
||||
0886 |
EIP: DLR topology (2 p)* |
- |
||||
0887 |
EIP: DLR state (2 p)* |
- |
||||
0889 |
EIP: Interface status (2 p)* |
- |
||||
0890 |
EIP: Interface control (2 p)* |
9 |
||||
SCA06 |
- - - - |
USB |
WEG USB Driver |
- - - - |
- - - - - |
- - - - - |
SCA06 + ECO4 module |
- - - - |
0803 |
Eth:Baud rate |
0 = Auto |
||
0806 |
Eth:Modbus TCP Timeout |
0 |
||||
0810 |
Eth:IP Address Config |
1 = DHCP |
||||
0815 |
Eth:CIDR Sub-net |
24 = 255.255.255.0 |
||||
0816 |
Eth:Gateway 1 |
0 |
||||
0817 |
Eth:Gateway 2 |
0 |
||||
0818 |
Eth:Gateway 3 |
0 |
||||
0819 |
Eth:Gateway 4 |
0 |
||||
0820..0831 |
Eth:Read Word #5..#16 |
0 |
||||
0835..0846 |
Eth:Write Word #5..#16 |
0 |
||||
0849 |
Eth:Configuration Update |
0 = Normal Operation |
||||
PLC300 |
- - - - |
USB |
WEG USB Driver |
- - - - |
- - - - - |
- - - - - |
SSW900 |
- - - - |
USB |
WEG USB Driver |
- - - - |
- - - - - |
- - - - - |
SSW900 + SSW900-CETH-IP-N module |
- - - - |
C8.3.1 |
Update Configuration |
0 = Normal Operation |
||
C8.3.2 |
Address |
63 |
||||
C8.3.3 |
Baud Rate |
3 = Autobaud |
||||
C8.3.4 |
IP Address Configuration |
1 = DHCP |
||||
C8.3.5 |
IP Address |
0.0.0.0 |
||||
C8.3.6 |
CIDR |
24 = 255.255.255.0 |
||||
C8.3.7 |
Gateway |
0.0.0.0 |
||||
C8.3.8 |
Station Name Suffix |
0 |
||||
SSW900-CETH-W |
SSW900 + SSW900-CETH-W module |
- - - - |
0798 |
Web Server Config |
0 = Disabled |
|
0846 |
IP Address in Use |
0.0.0.0 |
||||
0850 |
IP Address Config |
1 = DHCP |
||||
0852 |
IP Address |
0.0.0.0 |
||||
0855 |
CIDR Sub-net |
24 = 255.255.255.0 |
||||
0856 |
Gateway |
0.0.0.0 |
||||
0860 |
MBTCP: Communication Status |
0 = Disabled |
||||
0863 |
MBTCP: Active Connections |
0 |
||||
0865 |
MBTCP: TCP Port |
502 |
||||
0866 |
MBTCP: Unit ID |
255 |
||||
0868 |
MBTCP: Timeout |
0.0 |
||||
0869 |
EIP Master Status |
0 = Run |
||||
0870 |
EIP Communication Status |
0 = Disabled |
||||
0871 |
EIP Data Profile |
10 = Configurable I/O Data |
||||
0888 |
Ethernet Baud rate |
0 = Auto |
||||
0889 |
Ethernet Interface Status |
0 |
|
NOTE! Please refer to the equipment or accessory manual for more information. |
* To perform a firmware update, consider another parameterization, according to the instructions: Firmware Download.